Megger DET4TCR2 Rechargeable Earth Tester


Description


 

Megger DET4TCR2 Rechargeable Earth Tester Details

This instrument is a rechargeable version of Megger’s DET4TC2 Earth tester and contains all of the features found on the standard battery device such as 2, 3 and 4 point testing and attached rod technique via the use of an optional clamp.

The DET4TCR2’s interface has been designed to be as simple to use as possible. All you have to do is connect up the necessary test leads, use the rotary dial to select which test procedure you want, adjust the frequency and the voltage using labelled buttons then press the large test button. You can also toggle the backlight of the LCD display on off for use in darkened conditions.

Other included features of the DET4TCR2 include the ability to automatically evaluate the connection status of C stake and P stakes. When this test is performed it will display the connection/condition of each connected stake on the LCD display for easy referencing. The tester also features automatic noise checking, with rejection from 40V peak to peak.

The Megger DET4TCR2 also can test resistance with range of 0.01 to 200KΩ, runs on 8 x rechargeable batteries and is in accordance with IEC61326-1.

Megger DET4TCR2 Earth Tester Key Features

  • Automatic C and P stake checks
  • Automatic noise check with rejection at 40V peak to peak
  • 2 wire, 3 wire and 4 wire testing with no shorting links required
  • Stakeless measurement possible via optional ICLAMP or VCLAMP
  • No disconnect testing (ART) through use of optional ICLAMP
  • Ground current measurement range of 0.5mA to 19.9A
  • Ground voltage range of 0 to 100V AC
  • IP54 ingress protection

Full List of Products Included

  • Megger DET4TCR2 Earth Tester
  • Hard Carry Case
  • Stake and Wire Kit (15m, 10, 10m, 3m)
  • External AC/DC Charger
  • Calibrate Certificate
  • Rechargeable Batteries

Technical Specs

 


 

Part Code: 1000-346

Megger DET4TCR2 Technical Specifications

Ingress Protection IP54
 C Stake, P Stake and Noise Checks  Automatic
Noise Rejection 40V peak to peak
2 wire, 3 wire and 4 wire tests Yes with no shorting links required
No disconnect testing (ART) Yes, with ICLAMP
Stakeless Measurements Yes, with ICLAMP and VCLAMP
Instrument Output Voltage: ±25 V or ±50 V at 94 Hz, 105 Hz, 111 Hz and 128 Hz
Current: 4.5 mA or 0.45 mA or 0.045 mA
Ground Current Range with Clamp 0.5 mA to 19.9 A
Ground Current Accuracy 5% ±3 digits
Ground Voltage Range 0 to 100V AC
Ground Voltage Accuracy 2% ±2 V
Resistance Range 0.01 Ω to 200 kΩ
Resistance Accuracy 2P measurements: 2% ±3 digits
3P measurements: 2% ±3 digits
4P measurements: 2% ±3 digits
ART measurements: 5% ±3 digits
Stakeless measurements: 7% ±3 digits
Maximum Probe Resistance Rp limit: 200 kΩ (50 V output voltage)
Rc limit: 200 kΩ (50 V output voltage)
Limits reduced to 100 kΩ for 25 V output voltage
Limits reduced to 5 kΩ for 0.01 Ω resolution
Display 31⁄2 digit high contrast liquid crystal, backlit
Battery Type DET4TC2: 8 off AA (LR6) cells
DET4TCR2: 8 off AA (LR6) NiMH rechargeable cells
Operating Temperature Range -15 °C to +55 °C / 5 °F to 131 °F
Storage Temperature Range -40 °C to +70 °C / -40 °F to 158 °F
Safety Complies with the requirements of IEC 61010-1 100V CAT IV
between terminal pairs
EMC In accordance with IEC61326-1
Standards Compliance Complies with the requirements of KEMA K85B
Complies with the following parts of EN61557, “Electrical safety in low voltage distribution systems
up to 1000 V a.c. and 1500 V d.c. – Equipment for testing, measuring or monitoring of protective
measures”.
Part 1 – General requirements
Part 5 – Resistance to earth
Dimensions 203 mm x 148 mm x 78 mm (8 in x 5.8 in x 3 in)
Weight 1kg (2.2lb)

 

Based on 0 reviews